RE: With an Inverter/Charger is it possible to use separate charge and load bus bars?

Hi Tom, This is a good analysis of the different options. We all had to make that decision base on our perception / requirements in terms of usabil...

Il y a 4 mois
Répondre
RE: Cant get 0% SOC

You are right, during the "once a month charge to 100%" that is programmed in the CCM parameters, the charge is stopped by CCM only when the battery i...

Il y a 9 mois
Répondre
RE: Cant get 0% SOC

Hi @daniel There is one situation where the SOC is adjusted to 100% even though the battery did not reach the full state. The displayed SOC is an ...

Il y a 10 mois
Répondre
RE: How to connect external system to use the BMS data?

I understand that you want to access the BMS live data so that you can display it on a custom dashboard that you would create with a Raspberry. The ...

Il y a 10 mois
Répondre
RE: Cant get 0% SOC

Hi @daniel, I will first explain the "empty battery" feature (how it works) then we will diagnose your situation. "Empty Battery" feature: The...

Il y a 10 mois
Répondre
RE: gerer un deuxieme inverter avec la SOC

Bonjour Guy, Tu peux définir les consignes envoyées au Cerbo pour le nouveau trigger. Regardes dans le manuel du Moniteur section 9.3 (Limites de c...

Il y a 10 mois
Répondre
RE: Possible BMS setting for solar always "on"

Bonjour Michel, Your objective to charge the lead-acid batteries is achieved when R1 is open and R3 is closed (which are set that way by the TAO BMS...

Il y a 11 mois
Répondre
RE: Possible BMS setting for solar always "on"

Bonjour Michel, Can you specify if you want the solar panels to charge the two lead-acid batteries either: via the Argofet (in that case connect...

Il y a 11 mois
Répondre
RE: New monitor calculations based on incorrect battery capacity

Hi Tom, I agree with you that what you observe coud be caused by the BMS using a wrong battery capacity. But as you have checked both the nominal ca...

Il y a 1 an
Répondre
RE: 2 Batteries in parallel?

Hi Jens, I have summarized here the potential issues when connecting two or more drop-in batteries in parallel. Some of these issues might be reduc...

Il y a 1 an
Répondre
RE: Multiplus throwing low battery alarm errors - 620amp @ 12v LifePO4 (8 x Prism cells - 2P4S)

Hi Andres, Same behavior for my Multiplus when I start the water maker - like Jens I ignore it and recovers on its own. Now I run the generator j...

Il y a 1 an
Répondre
RE: TAO II - 12V - 600Ah - 2p4s - Victron Multiplus, MPPT, Orion Tr - Balmar Alternators & regulators

Hi Jens, thanks for the feedback. May I use your Technical Documentation as a template for our installation? Yes you can. I will forward by ...

Il y a 1 an
Répondre
RE: Foxy Kitty - 12V - 700Ah - 2x Alt + Balmar Reg / 3x Victron MPPT / Superwind 350 + Reg / Victron Quattro

A thread in the support forum has reinforced the utility of having comprehensive documentation of your system, including design principles and actual ...

Il y a 1 an
Répondre
RE: Significant voltage drop

To better understand what has been happening I had a look at your battery's remote dashboard to explore the most obvious possible causes for a voltage...

Il y a 1 an