RE: Monitor disconnected from BMS

The error message in the log is due to the Monitor not being able to connect to the BMS. So the issue would come from either the cable or the BMS its...

Il y a 2 ans
Répondre
RE: Monitor disconnected from BMS

Hi Andres, Thanks for all the details / screenshots. I will look into the error message later this afternoon and get back to you. Have you tried ...

Il y a 2 ans
Répondre
RE: Gestion du 100% SOC

Soit tu te connectes au tableau de bord local avec l'application web (PC ou tablette connectée au même réseau Wifi que le BMS / ou utilisation du poin...

Il y a 2 ans
Répondre
RE: Gestion du 100% SOC

Une règle de base pour les batteries au lithium: ne jamais faire confiance à un préréglage "Lithium" d'un équipement! Il faut décider des plages et ...

Il y a 2 ans
Répondre
RE: Gestion du 100% SOC

Il devait y avoir un déséquilibre qui s'est résorbé car le réglage du 100% SOC est OK et c'est une cellule qui est arrivée en tension haute qui a décl...

Il y a 2 ans
Répondre
RE: Gestion du 100% SOC

Bonjour Dominique, Cela semble indiquer que les chargeurs ont été coupés par un "trigger" de tension haute (cellule à 3.55 volt) avant que les condi...

Il y a 2 ans
Répondre
RE: Initial cell balancing

Thanks for sharing. There was a large unbalance of 24Ah and it is normal it takes a long time even with a 2A balancing current. Imagine how long i...

Il y a 2 ans
Répondre
Répondre
RE: CAN bus parameters sent to Cerbo do not update after disabled charge enabled

OK, I stay tuned. I have made some tests on my side trying to reproduce using a charge profile with only 1% difference between low and high SOC, bu...

Il y a 2 ans
Répondre
RE: CAN bus parameters sent to Cerbo do not update after disabled charge enabled

Hi Tom, Since when does it do that? Could there be a trigger that is active? Can you send: a screenshot of the CANbus limits you have set ...

Il y a 2 ans
Répondre
RE: how to switch spare battery in case of UVP/OVP

Hi @molly If you can control the chargers individually to stop charge (remote control or CANbus), the easiest is to have a single OVP/UVP power rela...

Il y a 2 ans
Répondre
RE: Help please - monitor unresponsive

When the Monitor restarts it does some internal cleanup and it is a good idea to restart the Monitor from time to time (every 3-4 months to be on the ...

Il y a 2 ans
Répondre
RE: Help please - monitor unresponsive

Hi Darren, Sorry to hear about that problem. It seems you have done everything right to try restart the Monitor. Next is to try a hard reset: ...

Il y a 2 ans
Répondre
RE: LifePo charged by alternator

The Orion DC/DC charger would be activated by the engine contact key. You could also have the BMS activate the DC/DC charger when the lithium battery...

Il y a 2 ans
Répondre
RE: charging questions again..

charging voltage: Let’s say we have 100%SOC at 13.6V…If I understand correctly, it is possible to charge the battery with a lower voltage than 13.6V a...

Il y a 2 ans