RE: Rec / Tao - 12V - 280Ah - Alt + Wakespeed WS500 / Victron MPPT, DC-DC, Phoenix 120vac, Emergency Switch

Thanks for sharing. I will unfortunately have to remove the uploaded file that is copyrighted - I doubt we have permission to have that file on a pub...

Il y a 3 ans
Répondre
RE: Rec / Tao - 12V - 280Ah - Alt + Wakespeed WS500 / Victron MPPT, DC-DC, Phoenix 120vac, Emergency Switch

Regarding the alternator regulator for LFP you are right. This is what you need: the ability to adjust bulk / absorption voltage a temperature s...

Il y a 3 ans
Répondre
RE: What is pre-charge and how it works...

Hi Tom, A 5000 watt inverter must have quite large input capacitors that will generate significant inrush current as soon as it is connected - wheth...

Il y a 3 ans
Répondre
RE: Rec / Tao - 12V - 280Ah - Alt + Wakespeed WS500 / Victron MPPT, DC-DC, Phoenix 120vac, Emergency Switch

Hi Rick, Very interesting thread on DIYsolar... a bit long and I admit I did not go through the 22 pages! yes, the TAO BMS can control both the ...

Il y a 3 ans
Répondre
RE: White Hawk - 12V - 920Ah - Alternators with Balmar MC614 regulators, Blue Sky MPPT Solar

Hi John, Battery nominal capacity: You should set the battery nominal capacity to the usable capacity of your battery based on the charge and load...

Il y a 3 ans
Répondre
RE: BMS concerning a 2x2P16S bank

If you are talking about connecting "via Internet", there is no need to connect the computer to the BMS. All WiFi and Internet connection is handled ...

Il y a 3 ans
Répondre
RE: Foxy Kitty - 12V - 700Ah - 2x Alt + Balmar Reg / 3x Victron MPPT / Superwind 350 + Reg / Victron Quattro

1 - For CANbus connectivity, do both monitors need to connect to the Cerbo? Or does only one BMS (the master) monitor connect to the Cerbo and the oth...

Il y a 3 ans
Répondre
RE: BMS concerning a 2x2P16S bank

Quote from yaq on 22/09/2022, 11:32 pm In the case of 2 cells in parallel, rather than connecting the wires of the bms on one of the two terminals o...

Il y a 3 ans
Répondre
RE: BMS concerning a 2x2P16S bank

Quote from yaq on 22/09/2022, 11:10 pm - So I connect the led panels on the RJ45 and the monitors on the RJ11, Yes then a CAN cable in daisy...

Il y a 3 ans
Répondre
RE: BMS concerning a 2x2P16S bank

The Monitor and the LED panel do not use the same method to connect to the BMS. The Monitor is a serial communication (RS485) while the LED panel is ...

Il y a 3 ans
Répondre
RE: SOH calculation looks strange (or very scary)

SOH showed 100% after a few minutes of changing the charging voltage to 13.8V That is quite strange. For the SOH to change the BMS must have reca...

Il y a 3 ans
Répondre
RE: SOH calculation looks strange (or very scary)

My best guess is that for a while the SOC calculated by the BMS has been out by a significant amount. So when the BMS thought the SOC was within a va...

Il y a 3 ans
Répondre
RE: Shore power charge voltage setting experiments

In normal conditions the cells resistance varies slowly over time and I do not think it can go down - it makes sense that it does only get worse over ...

Il y a 3 ans
Répondre
RE: Foxy Kitty - 12V - 700Ah - 2x Alt + Balmar Reg / 3x Victron MPPT / Superwind 350 + Reg / Victron Quattro

I now have 500A shunts. The CAN interface is managed by the Monitor, so you need one Monitor for each battery (both BMS are the same and the master ...

Il y a 3 ans
Répondre
RE: Foxy Kitty - 12V - 700Ah - 2x Alt + Balmar Reg / 3x Victron MPPT / Superwind 350 + Reg / Victron Quattro

Why would you need two BMV712 to monitor battery voltage, current and SOC? Each BMS will do that for the battery it monitors. I think each battery ...

Il y a 3 ans